I don't see how this would save you money as you are charged for kWhr not for the Voltage. Admittedly some appliances (inductive) will use less power if the voltage is reduced but anything that has a SMPS will use just the same amount of power.
Your electric oven and shower will use less but your TV, computers etc won't. Also I see from the specs that it will switch modes when current increases, so will probably switch out when you turn on the shower anyway.
You also have to ask, what is the efficiency (and hence running cost) of the unit? What is the initial cost (and therefore payback period)?
Been offered one really cheap (brand new the guy has a spare £80) and am going to install it mainly as when my solar PV operates at really sunny and pushes out over 2.5Kw my mains voltage rises to 250V and the UPS starts kicking in.
so my main drive for fitting one is to give the PSU's a little break as i anticipate running at the higher end of the rating will shorten life.
I noticed as well it goes into bypass if the load exceeds 40A thats about 9KW i only ever hit this when running 4 ovens (i have 2 kitchens as we have a granny annexe). Typically i inly peak at 6 and thats when we have washing machine and tumble and dishwasher on (wife on a saturday)
I have a very accurate meter and set up some tests to "see" how much power stuff drew with unit on and in bypass mode.
results were intresting.
tv's typically 5% lower (2-7% depending on size)
computer's same no saving.
hoover 9% lower
pond pump 8% lower (this is a 100w pump that runs 24/7 was reading 102W now reading 94W)
freezer 3% lower, fridge 5% lower.
I did not test anything with a heating element as my thought are it would read lower just take longer to heat.
My immersun and UPS have since the unit has been fitted not reported high voltage. (which is good).
the unit itself is made up of a fixed ratio toroidal transformer, some electronics, what looks like some seriously rated surge protection and some really heavy duty relays (so unit can go into bypass mode)
with an input voltage of 240v it reduces it to 220 at 250V it reduces it to 232V. so about an 8% reduction
the intresting part is every 3-4 day's i used to have to reset my SKYHD box and my AV amp every 2-3 days, so far neither has needed any resetting.
Member for
14 years 5 monthsI don't see how this would
I don't see how this would save you money as you are charged for kWhr not for the Voltage. Admittedly some appliances (inductive) will use less power if the voltage is reduced but anything that has a SMPS will use just the same amount of power.
Your electric oven and shower will use less but your TV, computers etc won't. Also I see from the specs that it will switch modes when current increases, so will probably switch out when you turn on the shower anyway.
You also have to ask, what is the efficiency (and hence running cost) of the unit? What is the initial cost (and therefore payback period)?
Member for
15 years 10 monthsThanks Mark
That pretty much mirrors my findings.
Been offered one really cheap (brand new the guy has a spare £80) and am going to install it mainly as when my solar PV operates at really sunny and pushes out over 2.5Kw my mains voltage rises to 250V and the UPS starts kicking in.
so my main drive for fitting one is to give the PSU's a little break as i anticipate running at the higher end of the rating will shorten life.
I noticed as well it goes into bypass if the load exceeds 40A thats about 9KW i only ever hit this when running 4 ovens (i have 2 kitchens as we have a granny annexe). Typically i inly peak at 6 and thats when we have washing machine and tumble and dishwasher on (wife on a saturday)
Dean
Member for
15 years 10 monthsupdate
Well i went for a dearere higher rated unit.
I have a very accurate meter and set up some tests to "see" how much power stuff drew with unit on and in bypass mode.
results were intresting.
tv's typically 5% lower (2-7% depending on size)
computer's same no saving.
hoover 9% lower
pond pump 8% lower (this is a 100w pump that runs 24/7 was reading 102W now reading 94W)
freezer 3% lower, fridge 5% lower.
I did not test anything with a heating element as my thought are it would read lower just take longer to heat.
My immersun and UPS have since the unit has been fitted not reported high voltage. (which is good).
the unit itself is made up of a fixed ratio toroidal transformer, some electronics, what looks like some seriously rated surge protection and some really heavy duty relays (so unit can go into bypass mode)
with an input voltage of 240v it reduces it to 220 at 250V it reduces it to 232V. so about an 8% reduction
the intresting part is every 3-4 day's i used to have to reset my SKYHD box and my AV amp every 2-3 days, so far neither has needed any resetting.
Dean